The RCL series racks are designed for our G9E cabinets.
Each rack is assembled with switch, fuses and single-phase capacitors.
Banks with blocking reactors (AAR/ … series) are available for high harmonic current content
Reactors are provided of a safety over-temperature probe to trip down banks
Capacitance tolerance -5% / +10
Rated frequency 50Hz
Supply Three-phase + ground
Max. allowable voltage 1,1 Un (max. 8 /24 h)
Safety device Overpressure disconnector
Auxiliary circuits 230 Vac (110 Vac on request)
RCL–AAR/138:
THD(I)max. = 100% on the network
THD(U)max. = 6% on the network
RCL–AAR/D20:
THD(I)max. = 100% on the network
THD(U)max. = 20% on the network